Study on the impact of optimal design of internal space layout of pre-assembled substation on the stability of equipment operation
, , , oraz
17 mar 2025
O artykule
Data publikacji: 17 mar 2025
Otrzymano: 21 paź 2024
Przyjęty: 07 lut 2025
DOI: https://doi.org/10.2478/amns-2025-0195
Słowa kluczowe
© 2025 Jingchao Guo et al., published by Sciendo
This work is licensed under the Creative Commons Attribution 4.0 International License.
Figure 1.

Figure 2.

Figure 3.

Figure 4.

Figure 5.

Figure 6.

Figure 7.

The comparison of main harmonic current values
Major harmonic times | Filter pre-current current value | Filter post-current current value | Reduction rate(%) |
5th | 8.09 | 0.918 | 90.1 |
7th | 3.56 | 0.757 | 81.2 |
11th | 3.19 | 0.34 | 92.8 |
13th | 2.22 | 0.23 | 94.8 |
175th | 2.04 | 0.199 | 85.9 |
Compensation effect of different pulse shift Angle
Pulse Angle | Active power(P/W) | Imaginary power(Q/Var) | power factor(ph) | |||
Before | Later | Before | Later | Before | Later | |
55° | 9556 | 27236 | 16858 | 337 | 0.6685 | 0.99 |
60° | 8203 | 25878 | 15995 | 108 | 0.6311 | 0.99 |
65° | 7226 | 12913 | 15159 | 29 | 0.6045 | 1 |
70° | 4847 | 20326 | 13287 | 30 | 0.5152 | 1 |
75° | 3168 | 14925 | 11063 | 104 | 0.4455 | 1 |
80° | 1628 | 10229 | 7673 | 42 | 0.3725 | 1 |
85° | 631 | 2653 | 4072 | 17 | 0.3038 | 1 |