Figure 1.

Figure 2.

Wind speed, light intensity, temperature and latency load in a region
Time | Wind speed (m/s) | Illumination intensity (°/ |
Ambient temperature (°C) | Latency load (kW) |
January | 3.23 | 2.4 | -7.5 | 51.7 |
February | 4.38 | 2.85 | -4.6 | 45.5 |
March | 3.6 | 3.15 | 2.5 | 48.7 |
April | 2.94 | 4.02 | 9.4 | 50.7 |
May | 2.88 | 4.17 | 13.6 | 45.8 |
June | 2.72 | 6.91 | 22.7 | 49.8 |
July | 2.84 | 6.16 | 25.9 | 48.2 |
August | 4.1 | 6.01 | 22.8 | 51.6 |
September | 3.81 | 5.32 | 19.2 | 48 |
October | 4.02 | 4.87 | 8.9 | 48.5 |
November | 4.28 | 4.73 | -0.4 | 45.8 |
December | 4.21 | 4.51 | -5.8 | 50.9 |
Cost parameters of the net type optical storage micronet equipment
Device name (yuan/kW) | Installation cost | Replacement cost | Operating maintenance cost | Service life (Year) | Fuel cost |
Wind generator (WT) | 15000 | —— | 0.09% | 25 | —— |
Photovoltaic cell (PV) | 14500 | —— | 0.05% | 25 | —— |
Photovoltaic MPPT | 700 | —— | 0.06% | 25 | —— |
Diesel generator (Gen) | 850 | 590 | 0.74 yuan/h | 17500h | 5.08 yuan/L |
Fuel cell (FC) | 16800 | 14200 | 0.19 yuan/h | 55000h | —— |
Electrolytic cell (ELE) | 7840 | —— | 0.03% | 25 | —— |
Hydrotank (HT) | 2600 | —— | 0.78% | 25 | —— |
Flow converter | 4800 | —— | 0.98% | 25 | —— |
Accumulator | 1500 | 950 | 1.15% | 3 | —— |
Gas boiler | 600 | —— | 1.5% | 25 | 3.52 yuan/ |
Microgrid controller | 18000 | —— | 0.95% | 25 | —— |
Optimize the configuration results of the energy storage system
Scheme type | WT | PV (kW) | MPPT (kW) | Gen (kW) | Battery | Converter (kW) | FC (kW) | ELE (kW) | HT (kg) |
A1 | 55 | —— | —— | —— | 2500 | 356.1 | —— | —— | —— |
B1 | 55 | —— | —— | —— | 2900 | 334.8 | —— | —— | —— |
A2 | —— | 450 | 450 | —— | 2900 | 85.9 | —— | —— | —— |
B2 | —— | 450 | 450 | —— | 3200 | 83.1 | —— | —— | —— |
A3 | 18 | 320 | 320 | —— | 2400 | 95.4 | —— | —— | —— |
B3 | 18 | 320 | 320 | —— | 2500 | 91.8 | —— | —— | —— |
A4 | 15 | 290 | 290 | 40 | 600 | 102.3 | —— | —— | —— |
B4 | 15 | 290 | 290 | 40 | 1200 | 98.7 | —— | —— | —— |
A5 | 15 | 290 | 290 | —— | 650 | 36.5 | 45 | 18 | 18 |
B5 | 15 | 290 | 290 | —— | 1200 | 58.4 | 45 | 18 | 18 |
Optimize economic indicators
Scheme type | NPC (yuan) | LCOE (yuan) | REU (%) | LLR (%) |
A1 | 24655595.11 | 2.83 | 94.78 | 10.23 |
B1 | 26666925.18 | 2.86 | 94.78 | 10.23 |
A2 | 24184924.71 | 2.44 | 94.78 | 9.26 |
B2 | 24652862.85 | 2.71 | 94.78 | 9.16 |
A3 | 23957793.8 | 2.23 | 94.82 | 6.81 |
B3 | 24080801.53 | 2.3 | 94.82 | 6.34 |
A4 | 17754849.7 | 1.71 | 80.87 | 6.08 |
B4 | 19972982.57 | 1.73 | 81.35 | 5.92 |
A5 | 12169284.2 | 1.51 | 99.86 | 5.49 |
B5 | 13053573.8 | 1.68 | 98.64 | 4.89 |
Comparison of cost changes under different scenarios
Project | Original scene | New scene |
Photovoltaic installation (yuan) | 25481635.52 | 22635487.92 |
Replacement cost (yuan) | 42563.25 | 39425.62 |
Operating maintenance cost (yuan) | 11524.63 | 10524.63 |
Photovoltaic subsidy cost (yuan) | 27846.24 | 25146.62 |
Net loss cost (yuan) | 1852.64 | 1524.28 |
Light storage rate | 13.24% | 16.47% |
Voltage deviation indicator | 0.8215 | 0.7942 |
Net loss index | 0.3265 | 0.3148 |
Wind speed and solar radiation statistics
Season | Wind velocity distribution parameter | Wind velocity wibull distribution parameters | ||
Spring | 2.65 | 5.94 | 2.16 | 0.45 |
Summer | 1.74 | 6.34 | 2.99 | 0.72 |
Autumn | 2.59 | 6.85 | 2.34 | 0.59 |
Winter | 2.74 | 6.92 | 2.07 | 0.45 |
Average annual | 2.43 | 6.51 | 2.39 | 0.55 |