Research on indoor light environment of gymnasium based on Ecotect simulation analysis
, y
24 mar 2025
Acerca de este artículo
Publicado en línea: 24 mar 2025
Recibido: 31 oct 2024
Aceptado: 19 feb 2025
DOI: https://doi.org/10.2478/amns-2025-0738
Palabras clave
© 2025 Shouyi Wang et al., published by Sciendo
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Figure 1.

Figure 2.

Simulation results of distributed skylight lighting at different angles
| Body model | Emin(lx) | Emax(lx) | Eave(lx) | U2 |
|---|---|---|---|---|
| parallel arrangement | 320 | 2010 | 1209.06 | 0.18 |
| 15° Angle arrangement | 320 | 2960 | 1609.29 | 0.15 |
| 30° Angle arrangement | 320 | 2120 | 1770 | 0.13 |
| 45° Angle arrangement | 360 | 3350 | 2094.98 | 0.12 |
Lighting simulation results at different heights
| Body model | Emin(lx) | Emax(lx) | Eave(lx) | U2 |
|---|---|---|---|---|
| H=14m | 130 | 1530 | 942.01 | 0.14 |
| H=16m | 130 | 1530 | 832.98 | 0.15 |
| H=18m | 100 | 1460 | 799.78 | 0.10 |
| H=20m | 90 | 1420 | 762.92 | 0.08 |
| H=22m | 100 | 1310 | 713.79 | 0.14 |
Summer stadium illuminance, lighting coefficient table (Unit:lx)
| test time | The average illumination value of the competition site is Eave 01 | Lighting factor of the competition venue | Audience area average illumination value Eave 02 | Lighting factor of spectator area | The average illumination value in the gymnasium Eave | Daylighting factor in the stadium |
|---|---|---|---|---|---|---|
| 9:00 | 20 | 1.35% | 18 | 1.45% | 19 | 1.32% |
| 11:00 | 16 | 0.79% | 32 | 1.24% | 28 | 1.08% |
| 13:00 | 150 | 6.67% | 72 | 2.02% | 92 | 3.68% |
| 15:00 | 6 | 0.58% | 15 | 1.85% | 5 | 1.32% |
| average value | 48 | 2.35% | 34.25 | 1.64% | 36 | 1.85% |
Transition season stadium illuminance, lighting coefficient table (Unit:lx)
| test time | The average illumination value of the competition site is Eave 01 | Lighting factor of the competition venue | Audience area average illumination value Eave 02 | Lighting factor of spectator area | The average illumination value in the gymnasium Eave | Daylighting factor in the stadium |
|---|---|---|---|---|---|---|
| 9:00 | 14 | 1.87% | 15 | 1.78% | 14 | 1.84% |
| 11:00 | 36 | 1.51% | 35 | 1.61% | 36 | 1.56% |
| 13:00 | 12 | 1.13% | 18 | 1.15% | 19 | 1.14% |
| 15:00 | 9 | 1.56% | 11 | 2.01% | 13 | 2.08% |
| average value | 18 | 1.52% | 20 | 1.64% | 21 | 1.66% |
Standard value of daylight factor
| Lighting class | Visual task classification | sidelighting | top daylighting | |||
|---|---|---|---|---|---|---|
| Operating accuracy | Identification minimum size (mm) | Minimum lighting factor (%) | Indoor Critical Illuminance (lx) | Average lighting factor (%) | Indoor Critical Illuminance (lx) | |
| I | special detailed | 5 | 250 | 7 | 350 | |
| II | Very delicate | 0.15 < |
3 | 150 | 4.5 | 225 |
| III | delicate | 0.3 < |
2 | 100 | 3 | 150 |
| IV | ordinary | 1.0 < |
1 | 50 | 1.5 | 75 |
| V | rough | 0.5 | 25 | 0.7 | 35 | |
Lighting simulation results with different area ratios
| Body model | Emin(lx) | Emax(lx) | Eave(lx) | U2 |
|---|---|---|---|---|
| Skylight area/competition hall area=0.15 | 18 | 900 | 318.4 | 0.09 |
| Skylight area/competition hall area=0.25 | 62 | 1300 | 621.45 | 0.11 |
| Skylight area/competition hall area=0.35 | 160 | 1640 | 988.61 | 0.16 |
| Skylight area/competition hall area=0.45 | 190 | 2190 | 1320 | 0.18 |
| Skylight area/competition hall area=0.55 | 250 | 2210 | 1651.67 | 0.19 |