Research on indoor light environment of gymnasium based on Ecotect simulation analysis

,  and   
Mar 24, 2025

Cite
Download Cover

Figure 1.

ECOTECT plug-in
ECOTECT plug-in

Figure 2.

Illuminance uniformity of stadium
Illuminance uniformity of stadium

Simulation results of distributed skylight lighting at different angles

Body model Emin(lx) Emax(lx) Eave(lx) U2
parallel arrangement 320 2010 1209.06 0.18
15° Angle arrangement 320 2960 1609.29 0.15
30° Angle arrangement 320 2120 1770 0.13
45° Angle arrangement 360 3350 2094.98 0.12

Lighting simulation results at different heights

Body model Emin(lx) Emax(lx) Eave(lx) U2
H=14m 130 1530 942.01 0.14
H=16m 130 1530 832.98 0.15
H=18m 100 1460 799.78 0.10
H=20m 90 1420 762.92 0.08
H=22m 100 1310 713.79 0.14

Summer stadium illuminance, lighting coefficient table (Unit:lx)

test time The average illumination value of the competition site is Eave 01 Lighting factor of the competition venue Audience area average illumination value Eave 02 Lighting factor of spectator area The average illumination value in the gymnasium Eave Daylighting factor in the stadium
9:00 20 1.35% 18 1.45% 19 1.32%
11:00 16 0.79% 32 1.24% 28 1.08%
13:00 150 6.67% 72 2.02% 92 3.68%
15:00 6 0.58% 15 1.85% 5 1.32%
average value 48 2.35% 34.25 1.64% 36 1.85%

Transition season stadium illuminance, lighting coefficient table (Unit:lx)

test time The average illumination value of the competition site is Eave 01 Lighting factor of the competition venue Audience area average illumination value Eave 02 Lighting factor of spectator area The average illumination value in the gymnasium Eave Daylighting factor in the stadium
9:00 14 1.87% 15 1.78% 14 1.84%
11:00 36 1.51% 35 1.61% 36 1.56%
13:00 12 1.13% 18 1.15% 19 1.14%
15:00 9 1.56% 11 2.01% 13 2.08%
average value 18 1.52% 20 1.64% 21 1.66%

Standard value of daylight factor

Lighting class Visual task classification sidelighting top daylighting
Operating accuracy Identification minimum size (mm) Minimum lighting factor (%) Indoor Critical Illuminance (lx) Average lighting factor (%) Indoor Critical Illuminance (lx)
I special detailed d ≤ 0.15 5 250 7 350
II Very delicate 0.15 < d ≤ 0.3 3 150 4.5 225
III delicate 0.3 < d ≤ 1.0 2 100 3 150
IV ordinary 1.0 < d ≤ 5.0 1 50 1.5 75
V rough d > 5.0 0.5 25 0.7 35

Lighting simulation results with different area ratios

Body model Emin(lx) Emax(lx) Eave(lx) U2
Skylight area/competition hall area=0.15 18 900 318.4 0.09
Skylight area/competition hall area=0.25 62 1300 621.45 0.11
Skylight area/competition hall area=0.35 160 1640 988.61 0.16
Skylight area/competition hall area=0.45 190 2190 1320 0.18
Skylight area/competition hall area=0.55 250 2210 1651.67 0.19